Remote sites

Remote monitoring power is a winter energy problem.

Use the continuous load, communications peaks, local winter resource, battery temperature, access interval, and required uptime.

Direct answer

A 15 W continuous monitoring load uses 360 Wh per day. At 2.0 winter peak sun hours and a 0.78 derate, screen about 250 W of panel and a 12 V 300 Ah AGM bank for five days at 50% usable depth.

Before the hardware

Collect these four inputs.

  1. 01Continuous load
  2. 02Winter resource
  3. 03Battery temperature
  4. 04Visit interval

Decision table

Winter sizing table

Preliminary five-day AGM screen at 12 V, 2.0 peak sun hours, and 0.78 derate
Continuous loadDaily energyScreened panelAGM bank at 50% usable
5 W120 WhAbout 100 WAbout 100 Ah at 12 V
15 W360 WhAbout 250 WAbout 300 Ah at 12 V
25 W600 WhAbout 440 WAbout 500 Ah at 12 V

The table is calculated from the published model, then rounded up. Site shade, snow, cold capacity, communications peaks, and uptime requirements can increase it.

What makes it work

Three choices that need to be checked together.

Winter array

Use local winter resource, shade, snow, tilt, and access, not an annual average.

View the category

Cold battery bank

Chemistry, usable depth, cold derating, enclosure, and visit interval set capacity.

View the category

Permanent protection

Disconnects, surge protection, fusing, grounding, and enclosure follow the site risk.

View the category

Remote power still needs inspections, battery checks, and written findings. For the critical-power side, review preventive field service for critical power equipment before setting the visit interval.

Help around the hardware

A product record does not replace a system review.

Free

Free sizing review

A load worksheet review with the assumptions, missing inputs, and a hardware direction.

See all services
Quoted

Custom battery bank assembly

Series or parallel configuration with cables cut, crimped, and labelled after compatibility review.

See all services

Prepare a request

The site does not store these entries. After validation, your email app opens a structured message that you can review before sending.

Keep checking

The method and terms used here.

Read the sizing method

See the assumptions, suppression rules, and evidence standard used here.

Read the guide

Check the energy glossary

Confirm the meaning of capacity, energy, current, and autonomy.

Read the guide

Honest limits

Know before you buy

  • The table is a winter screen, not an uptime guarantee.
  • Local shade, snow cover, cold battery capacity, communications peaks, and service interval must be measured.
  • Permanent remote installations require site-specific enclosure, protection, grounding, and maintenance planning.

Read the method and limits

Common questions

Short answers, limits included.

Why size from winter instead of annual solar?

A remote load must survive its worst required season. Annual average resource can hide the winter shortage.

Why use five days of autonomy?

It is the approved winter-critical screening assumption. The real visit interval and uptime target may require more or less.

Does the table include snow and shade?

No. It uses the published resource model. Site snow, horizon, shade, tilt, and soiling must be assessed.

Can this guarantee camera uptime?

No. Load peaks, communications, weather, battery temperature, equipment faults, and service access prevent a guarantee.